| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/26/2022 | Pool/Spa - Final/Barrier | Not Ready | ||
| 04/21/2023 | Pool/Spa - Final/Barrier | Re-inspection required | side gate does not self close & latch, patio slider does not have an alarm, sub-panel door does not open to 90 degrees, move sub-panel over to have clear 36” in front | |
| 04/24/2023 | Pool/Spa - Final/Barrier | Re-inspection required | 4/24/23: move the panel to the right so no piping or other equipment is located inside the dedicated panel board space per 2018 IRC E3405.4 & FIGURE E3405.1 pool heater condensate leg is required to be downstream of the heater shut-off valve. It is currently located in between two SO valves. Install a valve for stub up by south wall of back yard. |
|
| 05/02/2023 | Pool/Spa - Final/Barrier | Passed | all pool barriers compliant at time of final inspection. |