Inspection Status: Not Ready
Inspection History: COT - ENGR - Sign Electrical
| Date |
Description |
Inspector |
Results |
Comments |
| 10/27/2022 |
COT - ENGR - Sign Electrical |
|
Not Ready |
|
| 03/22/2022 |
COT - ENGR - Sign Electrical |
DROBERTS |
Partial Approval |
Entered by VVERA1 - IS PARTIAL, SEE THE ABOVE NOTES FOR ELECTRICAL ITEMS. |
| 11/02/2021 |
COT - ENGR - Sign Electrical |
DROBERTS |
Not ready for Inspection |
Entered by NGARCIA3 - SIGN ELECTRIC IS NOT READY AT THIS TIME. I WILL NEED PHOTOGRAPHS OF THE FUSE BOX WITH A DESIGNATED 20 AMP FUSE, A TIMER FOR THIS SIGN, AND A LOCKOUT SWITCH EITHER ON THE SIGN OR IN THE ELECTRICAL ROOM. ALSO A PHOTO CELL IS ON THIS SIGN TO CONTROL THE OPERATIONAL TIME, THIS IS NOT ALLOWED, PROVIDE A TIMER IN THE ELECTRICAL ROOM. |
| 10/25/2021 |
COT - ENGR - Sign Electrical |
DROBERTS |
Continued |
Entered by NGARCIA3 - CONTINUED, WILL BE RESCHEDULED FOR 10/27/2021 IN THE AM ALONG WITH ALL OTHERS.
|