Permit: T21OT00070

Parcel: 141366820


Addresses:

7401 S WILMOT RD


Inspection Status: Approved

Inspection History: SIGN SITE REVIEW

Permit Number - T21OT00070

Inspection Description - SIGN SITE REVIEW

Inspection Status - Approved

Date Description Inspector Results Comments
02/24/2021 SIGN SITE REVIEW Approved Resubmittal approved and permit issued for wall signs
02/24/2021 SIGN SITE REVIEW Approved
02/18/2021 SIGN SITE REVIEW Continued Resubmittal received
02/04/2021 SIGN SITE REVIEW Continued Resubmittal received 2/4/21 for wall signs
01/28/2021 SIGN SITE REVIEW Partial Approval RE: sign review
For: wall signs
AT: 7475 S Wilmot
Permit number: T21OT00070
Zone: PAD-7
Date: 1/28/2021
Reviewer: H. Thrall

Codes: Unified Development Code (UDC) 7A Sign Standards, National Electrical Code (NEC), International Building Code (IBC) 2018, and Tucson- Pima County Outdoor Lighting Code (OLC).
1. Property address has changed from 7401 S Wilmot to 7475 S Wilmot - please update plans and permit application.
2. Property within PAD-7 zoning
A. UDC 7A.10.2.B. - 3 to 1 ratio of sign area allowed for signs withing this site / acknowledged sign area proposed is within allowance of Wilmot street front property line of 309 x 3

3. Acknowledged building elevations provided prior to addition of signs, please provide diagram showing each full building elevations as it would appear with the signs on them after installed, and provide their heights off the ground to top of each sign. (Label signs as A, B, C, D, etc. to match the sign permit application.

4. Please revise plans to call out signs A, B, C, D - etc - to match the permit application, and revise the location map as well to call out signs.

5. Provide arrows from plan notes to the item referred to on the diagram.
Acknowledged information is there, but the plans are hard to read / refer to without this method of information referral for quick check.

6. Enlarge all notes note to a minimum of 12 point - hard to read - and for record.

7. National Electrical Code:
All notes provided, thank you.

8. Outdoor Lighting Code:
All notes provided, thank you.

9. International Building Code:
A. Provide mounting details (screw types, sizes, typical amount) from letter to raceway for each letter sign.
B. On sign B2 - appears to be cabinet sign, provide mounting clarification - as "raceway" is referenced.
10. On location map:
A. Call out street front property line frontage in enlarged lettering
B. Call out width of building elevation facing Wilmot
Revisions may be sent to Heather.Thrall@tucsonaz.gov