Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T21FC00830
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/04/2022 | FIRE - ALARM FINAL | Approved | ||
11/15/2021 | FIRE - ALARM FINAL | Prior to Final Inspectn | PROVIDE ADUBILITY / INTELLIGIBILITY METER AT FIRE ALARM FINAL ALL AREAS SHALL HAVE A MINIMU 55 DBA WITH THE DOOR CLOSED INCLUDING OFFICES. IF A/I AND DBA METER DO NOT MEET THE REQUIRED DBA YOU SHALL ADD ADITIONAL DEVICES TO THE OFFICES SUBJECT TO FIELD VERIFICATION TEST SHALL NOT BE PERFORMED VIA FACETIME PROVDE 1 FULL SIZE SET OF THESE APPROVED PLANS 24X36 IF DEVICES ARE ADDED AS BUILT DRAWINGS SHALL BE SUBMITTED TO TFD |