Inspection Status: Canceled
Inspection History: COT - FCON - Sprinkler - Final
| Date |
Description |
Inspector |
Results |
Comments |
| 11/04/2022 |
COT - FCON - Sprinkler - Final |
|
Canceled |
Inspection Canceled |
| 07/27/2023 |
COT - FCON - Sprinkler - Final |
|
Partial Pass |
North and east patio 5-6 heads are blocked by electrical conduit or lighting fixtures, Roll up door on north side of restaurant no coverage under door when open, bag covering head above bar. |
| 11/21/2023 |
COT - FCON - Sprinkler - Final |
|
Passed |
|