Permit: T21FC00800

Parcel: 11712001A

Inspection Status: Canceled

Inspection History: COT - FCON - Hood System - Final

Date Description Inspector Results Comments
11/07/2022 COT - FCON - Hood System - Final Canceled Inspection Canceled
11/18/2021 COT - FCON - Hood System - Final MROSS Partial Approval Entered by MROSS2 - -Need to verify that electrical outlet shuts off upon activation. -Hood system needs to be tied in to fire alarm panel. (in the basement parking area) -We tested all pipe, verified that gas and make up air shutdown. Exhaust fan did stay on.