Permit: T21FC00699

Parcel: 13215003L


Addresses:

770 E EVANS BL


Inspection Status: Not Ready

Inspection History: COT - FCON - Alarm - Final

Permit Number - T21FC00699

Inspection Description - COT - FCON - Alarm - Final

Inspection Status - Not Ready

Date Description Inspector Results Comments
10/26/2022 COT - FCON - Alarm - Final Not Ready
08/03/2022 COT - FCON - Alarm - Final JVINCENT Prior to Final Inspectn Entered by JVINCEN1 - Notes for inspector: -Revisions approved. -Verify mechanical permit/approval prior to approving/finaling this inspection.
09/23/2021 COT - FCON - Alarm - Final jvincent Prior to Final Inspectn Entered by JVINCEN1 - Notes for plan review only: Denied. Include the following information on resubmittal. IFC 5307.4.1. Include all information required in this section. Include on plans. Include sequence of operations that includes all requirements in IFC 5307.4.3, 5307.4.3.1, 5307.4.4 Reference mechanical permit that has been approved and meets the mechanical ventilation requirements, include on plans. 5307.4.4 Application is confusing. The submittal is for a CO2 gas detection system, however; application states it is for a sprinkler monitoring system to existing riser. Drawings do not clearly indicate all rooms. Unable to determine walls/doors on plans. Include legend on plan if using different markings for walls and doors. Include dimensions of every room that contains sensors/CO2 gas. Each sensor only covers 840 square feet. Add additional sensors to rooms larger than 840ft2 in revision.