Permit: T21FC00638

Parcel: 14027040C


Addresses:

2660 E BILBY RD

Inspection Status: Approved

Inspection History: FIRE SPKLR - OH PIPING & HYDRO

Date Description Inspector Results Comments
04/25/2022 FIRE SPKLR - OH PIPING & HYDRO Approved Tested the office area and restrooms with the rest of the builiding. 210psi.
04/22/2022 FIRE SPKLR - OH PIPING & HYDRO Denied No sprinkler heads in the bathrooms and the office area was not tied into the rest of the systems or pressurized. As Builds need to be submitted P2F due to the changes for the offices.