Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T21FC00446
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/07/2021 | FIRE - ALARM FINAL | Approved | ||
08/20/2021 | FIRE - ALARM FINAL | Partial Approval | As Builts Document box |
|
08/16/2021 | FIRE - ALARM FINAL | Partial Approval | -Submit As built plans -Breaker location needs to be labeled and locked -Panel communication cannot be by 2 phone lines -Need document cabinet -HVAC units need to be on so we can test shut down with duct detectors ITEMS TESTED -2 smoke detectors -4 pull stations -Sprinkler flow and tamper switch -All notification devices |
|
08/13/2021 | FIRE - ALARM FINAL | Denied | nobody from western on site |