Permit: T21FC00446

Parcel: 130140260


Addresses:

4152 E 22ND ST


Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T21FC00446

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/07/2021 FIRE - ALARM FINAL Approved
08/20/2021 FIRE - ALARM FINAL Partial Approval As Builts
Document box
08/16/2021 FIRE - ALARM FINAL Partial Approval -Submit As built plans
-Breaker location needs to be labeled and locked
-Panel communication cannot be by 2 phone lines
-Need document cabinet
-HVAC units need to be on so we can test shut down with duct detectors

ITEMS TESTED
-2 smoke detectors
-4 pull stations
-Sprinkler flow and tamper switch
-All notification devices
08/13/2021 FIRE - ALARM FINAL Denied nobody from western on site