Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T21FC00381
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/13/2022 | FIRE - ALARM FINAL | Approved | P2F FAROC | |
05/05/2022 | FIRE - ALARM FINAL | Partial Approval | 1-6 tested and passed. Mezzanine in 1-7 needs notification. | |
05/03/2022 | FIRE - ALARM FINAL | Partial Approval | Areas 1-4 and 1-5 are good Still need to test 1-6 and CEP |
|
04/28/2022 | FIRE - ALARM FINAL | Denied | Lateral fire/smoke damper detectors not shutting ndown RTU 7-1, 7-3, and 3-3 shall closte damper upon smoke detector activation. |
|
04/25/2022 | FIRE - ALARM FINAL | Correction Required | Corridor smokes im 2-2 through 2-5 need to be addressed properly. In 2-3 rooms 12 and 14 are mixed up In 2-4 c-section device labelling, NICU room smokes need to be addressed properly 2-5 all corridor and nurse station devices shall be addressed properly 2-2 devices shall correspond to signs identifying rooms. Devices in staff elevator hallway and public hallway shall be identified as such. ALL AHU AND FIRE/SMOKE, FIRE DAMPERS NEED TO BE TESTED, ALL DUCT SMOKE NEED TO BE TESTED AHU SHALL SHUT DOWN UPON ACTIVATION OF SMOKE DETECTOR IN DUCT IT SEVICES. |
|
04/22/2022 | FIRE - ALARM FINAL | Correction Required | Shall identify device locations as they exist, not how they were identified on prints | |
04/21/2022 | FIRE - ALARM FINAL | Partial Approval | All tampers, waterflow, low pressure and fire pump signals have been verified. | |
04/20/2022 | FIRE - ALARM FINAL | Cancelled | per contractor | |
03/31/2022 | FIRE - ALARM FINAL | Partial Approval | ONLY sprinkler monitorimg has been checked. Will need to be retested when new communicator is installed. 3 reinspection fees have ben aded |
|
03/23/2022 | FIRE - ALARM FINAL | Denied | Only stairwell 1 first and second floors have waterflows and tampers been tested. ALL OTHER RISERS INCLUDING DRY SYSTEMS NEED TO HAVE TAMPERS AND FLOWS VERIFIED. FIRE PUMP SIGNALS ALSO TO BE VERIFIED. |
|
03/22/2022 | FIRE - ALARM FINAL | Cancelled | ||
03/15/2022 | FIRE - ALARM FINAL | Cancelled | Per Ron | |
03/14/2022 | FIRE - ALARM FINAL | Cancelled | RE-OPEN |