Permit: T21FC00381

Parcel: 13608032A


Addresses:

2200 S HOUGHTON RD


Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T21FC00381

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/13/2022 FIRE - ALARM FINAL Approved P2F FAROC
05/05/2022 FIRE - ALARM FINAL Partial Approval 1-6 tested and passed. Mezzanine in 1-7 needs notification.
05/03/2022 FIRE - ALARM FINAL Partial Approval Areas 1-4 and 1-5 are good
Still need to test 1-6 and CEP
04/28/2022 FIRE - ALARM FINAL Denied Lateral fire/smoke damper detectors not shutting ndown RTU

7-1, 7-3, and 3-3 shall closte damper upon smoke detector activation.
04/25/2022 FIRE - ALARM FINAL Correction Required Corridor smokes im 2-2 through 2-5 need to be addressed properly.
In 2-3 rooms 12 and 14 are mixed up
In 2-4 c-section device labelling, NICU room smokes need to be addressed properly
2-5 all corridor and nurse station devices shall be addressed properly
2-2 devices shall correspond to signs identifying rooms.
Devices in staff elevator hallway and public hallway shall be identified as such.
ALL AHU AND FIRE/SMOKE, FIRE DAMPERS NEED TO BE TESTED,
ALL DUCT SMOKE NEED TO BE TESTED
AHU SHALL SHUT DOWN UPON ACTIVATION OF SMOKE DETECTOR IN DUCT IT SEVICES.
04/22/2022 FIRE - ALARM FINAL Correction Required Shall identify device locations as they exist, not how they were identified on prints
04/21/2022 FIRE - ALARM FINAL Partial Approval All tampers, waterflow, low pressure and fire pump signals have been verified.
04/20/2022 FIRE - ALARM FINAL Cancelled per contractor
03/31/2022 FIRE - ALARM FINAL Partial Approval ONLY sprinkler monitorimg has been checked.
Will need to be retested when new communicator is installed.
3 reinspection fees have ben aded
03/23/2022 FIRE - ALARM FINAL Denied Only stairwell 1 first and second floors have waterflows and tampers been tested.
ALL OTHER RISERS INCLUDING DRY SYSTEMS NEED TO HAVE TAMPERS AND FLOWS VERIFIED. FIRE PUMP SIGNALS ALSO TO BE VERIFIED.
03/22/2022 FIRE - ALARM FINAL Cancelled
03/15/2022 FIRE - ALARM FINAL Cancelled Per Ron
03/14/2022 FIRE - ALARM FINAL Cancelled RE-OPEN