Permit: T21FC00366

Parcel: 105110630

Inspection Status: Canceled

Inspection History: COT - FCON - Hood System - Final

Date Description Inspector Results Comments
11/07/2022 COT - FCON - Hood System - Final Canceled Inspection Canceled
08/05/2021 COT - FCON - Hood System - Final jfordney Partial Approval Entered by JFORDNE1 - Ansul system is functioning properly needs to be tied into FACP When makeup air is functioning, it must shut down upon Ansul activation Mount 2 K clas extinguishers OK TO OBTAIN TCO