Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/22/2021 | FIRE SPKLR - FINAL | Approved | ||
| 07/08/2021 | FIRE SPKLR - FINAL | Partial Approval | -Missing spare heads and wrench -FDC on rear of building needs to be repaired or replaced -Locking Knox FDC plugs are required -Tamper switch on valve and flow switch need to be connected to fire alarm -Need "FDC" sign at back of building -OK to install ceilings |