Permit: T21FC00283

Parcel: 11707226B


Addresses:

747 S 6TH AV


Inspection Status: Canceled

Inspection History: COT - FCON - Alarm - Final

Permit Number - T21FC00283

Inspection Description - COT - FCON - Alarm - Final

Inspection Status - Canceled

Date Description Inspector Results Comments
11/07/2022 COT - FCON - Alarm - Final Canceled Inspection Canceled
03/09/2022 COT - FCON - Alarm - Final IVR USER Cancelled Entered by IVR USER - IVRS - RI canceled
10/04/2023 COT - FCON - Alarm - Final Passed
10/03/2023 COT - FCON - Alarm - Final Partial Pass Tested all the following items and passed
-General Alarm smokes not related to elevator operation
-Pull Stations
-Water Flows and Tampers
-All notification

Items needed to address
-Add strobe in ADA restroom of Room 201
-Test supervisory smoke signals to the 14 resident suites on floors 2 and 3