Permit: T21FC00241


Addresses:

3550 E CORONA RD

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
08/23/2021 FIRE - ALARM FINAL Approved
08/04/2021 FIRE - ALARM FINAL Partial Approval -Still to be tested: Door releases x 4
-Pump test w/ valves & tampers
-Office area flow and tamper (valve is in pump room)
-R.O.C.

Items to correct:
-2 west exterior horn strobes (did not work, full of water)
-RTU C2 and D1 descriptors need to be switched
-10A & 10B RTU over office area descriptors changed
-Breaker lock and label in electric panel in pump room.