Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T21FC00241
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/23/2021 | FIRE - ALARM FINAL | Approved | ||
08/04/2021 | FIRE - ALARM FINAL | Partial Approval | -Still to be tested: Door releases x 4 -Pump test w/ valves & tampers -Office area flow and tamper (valve is in pump room) -R.O.C. Items to correct: -2 west exterior horn strobes (did not work, full of water) -RTU C2 and D1 descriptors need to be switched -10A & 10B RTU over office area descriptors changed -Breaker lock and label in electric panel in pump room. |