Permit: T21FC00181

Parcel: 125101480


Addresses:

3699 E BROADWAY BL


Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T21FC00181

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/02/2021 FIRE - ALARM FINAL Approved All duct smokes and RTU's checked out.
Alarm approved
04/29/2021 FIRE - ALARM FINAL Denied RTU 10 didn't shut down upon duct smoke activation
RTU's 8 and 3 were mislabled
Ensure all RTU's are properly labled on roof and at panel
Ensura all RTU shut down as intended
Reinspection fee added