Inspection Status: Canceled
Inspection History: COT - FCON - Hood System - Final
| Date |
Description |
Inspector |
Results |
Comments |
| 11/07/2022 |
COT - FCON - Hood System - Final |
|
Canceled |
Inspection Canceled |
| 01/11/2021 |
COT - FCON - Hood System - Final |
Mross |
Partial Approval |
Entered by MROSS2 - -submit as-built plans
-Hood system is required to be tied into the existing alarm panel
-Nozzle height is too low on center nozzles
-Right plenum nozzle is dirty, |