Permit: T21FC00004

Parcel: 13608032A


Addresses:

2200 S HOUGHTON RD


Inspection Status: Approved

Inspection History: FIRE SPKLR - OH PIPING & HYDRO

Permit Number - T21FC00004

Inspection Description - FIRE SPKLR - OH PIPING & HYDRO

Inspection Status - Approved

Date Description Inspector Results Comments
03/01/2022 FIRE SPKLR - OH PIPING & HYDRO Approved
11/17/2021 FIRE SPKLR - OH PIPING & HYDRO Partial Approval Fourth inspection
All OH piping and Hydro approved except:
-Mechanical/pump room
- ZoneC Everything south of restrooms next to elevators (including restroom foyers and penthouse
08/26/2021 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 1st floor approved EXCEPT:
-Stairwell 3 (fed from 2nd floor)
-Mechanical/pump room
-Cath room, staff lounge and electrical room in zone A to be verified at final. (pipes can be viewed through access hatch

2nd Floor:
-Zones A and B approved
Zone C:
-Rooms 2481-2483 OK to install ceiling (observe OH through access hatch at final)
-Rooms 2484-2492 OK to install ceiling OH & Hydro are good
2252 and Atrium are part of Zone C (yet to be completed
THIRD INSPECTION
08/25/2021 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 1st floor: Dry systems approved 40 psi since 8/23
2nd floor:
Zone A-missing hanger 2132
Zone B-1 leaking fitting
Zone C-not complete
This is sacond inspection
07/01/2021 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 1st floor approvwd except:
-Stairwell 3 (fed from 2nd level)
-All dry systems
-Mechanical room/Pump room
-Cath room, saff lounge, and electrical room in zone "A"
All 205 psi
06/30/2021 FIRE SPKLR - OH PIPING & HYDRO Cancelled Couldn't reach western states rep