Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
Case Number - T21DV04798
Inspection Description - INSP - INITIAL CODE ENFORCMENT
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/28/2021 | INSP - INITIAL CODE ENFORCMENT | Approved | The supervisor Martin Romero called that the property needed to be checked for electrical hazards. Arrived and the owners were on site and was able to check the violation. The issues were on the main electrical service panels were lacking the door panel covers and the dead fronts. The owners was able to find the door panels and 1-dead front. They have some romex that has been added to the panels and were not protected and were below 8'. Has some that has plastic pipes covering the romex on the other panel and showed what needs to be done. The owner was going to call a electrician to check the area and make the needed repairs. T.E.P. was on site at some time to place locking devices on the service side on the meter side where lacking. The owners are living in the house with the family. RV. |