Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/16/2021 | INSP - INITIAL CODE ENFORCMENT | Approved | ADDRESS: 1829 S CRAYCROFT RD OWNER/ OCCUPANT: ALWAHBAN REAL ESTATE LLC / AMOS BONYO STORE MGR CAUSE OF DAMAGE: COMMERICAL BUILDING FIRE LOCATION OF DAMAGE: SOUTH GARAGE BAY/ INTERIOR OF VEHICLE BUILDING: THERE IS FIRE AND HEAVY SMOKE DAMAGE TO THE SOUTH GARAGE BAY CEILING AND WALL COVERINGS. ELECTRICAL: THE FIRE DAMAGE ZONE HAS MULTIPLE ELECTRICAL DEVICES IN CLOSE PROXIMITY TO THE FIRE. MELTED ELECTRICAL WIRING EXPOSED. EXTENSION CORD ABUSE AND UNAPPROVED WIRING METHODS THROUGH OUT THE BUILDING. THE SERVICE PANEL IS MISSING THE PROTECTIVE COVER AND IS NOT CODE COMPLIANT. POWER WAS DISCONNECTED BY TEP AND METER WAS REMOVED. PLUMBING: N/A MECHANICAL: MILD TO MODERATE SMOKE DAMAGE TO VENTALATION AND COOLER IN CLOSE PROXIMITY TO FIRE DAMAGE ZONE. REMARKS: THIS COMMERCIAL BUILDING/GARAGE IS NOW CONDEMNED AND PERMITS ARE REQUIRED FOR REPAIRS AND RECONNECTION OF ELECTRICAL POWER. MUST HAVE LICENSED ELECTRICAL CONTRACTOR SUBMITT ON COMPANY LETTER HEAD THAT ALL CORRECTIONS HAVE BEEN MADE AND BUILDING IS SAFE TO ENERGIZE. STORE MGR WILL SECURE BUILDING. INSPECTOR POSTED BUILDING UNSAFE TO OCCUPY. WILL CLOSE CASE AT THIS TIME. |