Case: T21DV03792

Parcel: 122140110

Inspection Status: Approved

Inspection History: INSP - FOLLOW UP CODE ENFORCE

Date Description Inspector Results Comments
09/15/2021 INSP - FOLLOW UP CODE ENFORCE Approved PERMIT T21CM05907 FINAL CLOSE CASE
06/23/2021 INSP - FOLLOW UP CODE ENFORCE Approved THE COOLING WAS RESTORED BY A LICENSED CONTRACTOR.
THE ONSITE INSPECTION RESULTS ARE AS FOLLOWS: THERE ARE TWO ROOF MOUNTED MINI SPLIT UNITS WHICH HAVE BEEN INSTALLED WITHOUT PERMITS. THESE UNITS ARE NOT CODE COMPLIANT. THERE IS A 3 INCH ROUGH PENETRATION ABOVE THE GUTTER BOX WHERE THE REFRIGERANT LINES AND AN ELECTRICAL CABLE RUN INTO THE BUILDING. THESE LINES ARE NOT PROTECTED. THE MINI SPLIT UNITS CIRCUIT SHARES A NEUTRAL WITH TWO CIRCUIT BREAKERS ALSO NOT CODE COMPLIANT.

THERE IS A METALLIC CLAD CABLE INSTALLED WITHOUT A PERMITS, THE CABLE IS PRONE TO PHYSICAL DAMAGE AND NOT CODE COMPLIANT.

THERE IS A 30 AMP BREAKER WHICH ITS AMPACITY EXCEEDS THE CURRENT WIRING RATING, THE CIRCUIT WAS SHUT OFF.
06/22/2021 INSP - FOLLOW UP CODE ENFORCE Approved SPOKE TO TENANT SHE STATED COOLING IS WORKING BUT IS CONCERNED ABOUT THE CONTRACTOR REPORT STATING ELECTRICAL VIOLATIONS