Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FOLLOW UP CODE ENFORCE
Case Number - T21DV03792
Inspection Description - INSP - FOLLOW UP CODE ENFORCE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/15/2021 | INSP - FOLLOW UP CODE ENFORCE | Approved | PERMIT T21CM05907 FINAL CLOSE CASE | |
06/23/2021 | INSP - FOLLOW UP CODE ENFORCE | Approved | THE COOLING WAS RESTORED BY A LICENSED CONTRACTOR. THE ONSITE INSPECTION RESULTS ARE AS FOLLOWS: THERE ARE TWO ROOF MOUNTED MINI SPLIT UNITS WHICH HAVE BEEN INSTALLED WITHOUT PERMITS. THESE UNITS ARE NOT CODE COMPLIANT. THERE IS A 3 INCH ROUGH PENETRATION ABOVE THE GUTTER BOX WHERE THE REFRIGERANT LINES AND AN ELECTRICAL CABLE RUN INTO THE BUILDING. THESE LINES ARE NOT PROTECTED. THE MINI SPLIT UNITS CIRCUIT SHARES A NEUTRAL WITH TWO CIRCUIT BREAKERS ALSO NOT CODE COMPLIANT. THERE IS A METALLIC CLAD CABLE INSTALLED WITHOUT A PERMITS, THE CABLE IS PRONE TO PHYSICAL DAMAGE AND NOT CODE COMPLIANT. THERE IS A 30 AMP BREAKER WHICH ITS AMPACITY EXCEEDS THE CURRENT WIRING RATING, THE CIRCUIT WAS SHUT OFF. |
|
06/22/2021 | INSP - FOLLOW UP CODE ENFORCE | Approved | SPOKE TO TENANT SHE STATED COOLING IS WORKING BUT IS CONCERNED ABOUT THE CONTRACTOR REPORT STATING ELECTRICAL VIOLATIONS |