Case: T21DV03556

Parcel: 136281750


Addresses:

4425 S EVERGREEN AV


Inspection Status: Approved

Inspection History: INSP - FOLLOW UP CODE ENFORCE

Case Number - T21DV03556

Inspection Description - INSP - FOLLOW UP CODE ENFORCE

Inspection Status - Approved

Date Description Inspector Results Comments
01/07/2022 INSP - FOLLOW UP CODE ENFORCE Approved This case will be closed due to the tenant has complied with all that was asked to do and inspector Lopez was checking the site for compliance. Violation Abated, Close Case. RV.
07/15/2021 INSP - FOLLOW UP CODE ENFORCE Approved ENTERED EMAIL UPDATE REPORT
07/13/2021 INSP - FOLLOW UP CODE ENFORCE Approved RETURNED WARRANT
07/09/2021 INSP - FOLLOW UP CODE ENFORCE Approved Inspector Valdez had a warrant issued to have the property inspected. Inspector Valdez called T.P.D. on site to have the warrant served and to perserve the peace. Once the warrant served the inspection was allowed by the tenants who were served on site. The owner of the property was on site and was given a copy of the warrant and was on site until the inspection was completed. Those on site was T.P.D., Inspector Lopez, Inspector Vidal, Inspector Valdez, Case worker LaTonya Watkins who brought the people being cared for. There was approx. 9-people at the time of the inspection being cared for. The interior and the exterior was inspected with some of the items being corrected while on site.
07/09/2021 INSP - FOLLOW UP CODE ENFORCE Approved ONSITE INSPECTION UNDER AN ADMINISTRATIVE WARRANT: PRESENT WERE TUCSON POLICE SERGEANT HATCH, THE HOME OWNER ALONG WITH THE TENANT / MANAGER. CODE ENFORCEMENT STAFF WERE INSPECTOR LOPEZ, VIDAL AND MYSELF.
THE HOME IS A 3 BEDROOM HOME WITH, 3 TWINS BEDS IN THE MASTER BEDROOM, 2 TWINS IN THE 2 OTHER BEDROOMS.
THE DINING ROOM HAS BEEN ENCLOSED INTO A BEDROOM WHICH THE FEMALE MANAGER OCCUPIES.
THE ENCLOSED GARAGE HAS 4 BEDS WITH 3 OCCUPANTS.
THE CODE VIOLATIONS ARE AS FOLLOWS:
THE GARAGE HAS BEEN ENCLOSED WITHOUT A PERMIT, THE GARAGE CONVERSATION LACKS REQUIREMENTS PER THE 2018 INTERNATIONAL RESIDENTIAL CODE.
WALL OUTLETS NOT CODE COMPLAINT
CEILING LIGHT FIXTURE WIRING METHODS NOT CODE COMPLIANT
CLOSET WAS BUILT IN WITH LIGHTING NOT CODE COMPLIANT
UNPERMITTED HEATING AND COOLING, NEW MINI SPLIT UNIT INSTALLED WITHOUT A PERMIT AND NOT CODE COMPLIANT.
OUTLET WITH MISSING COVER PLATE
THE GAS FIRED FURNACE / AIR CONDITIONER HAVE BEEN INSTALLED WITHOUT A PERMIT AND ARE NOT CODE COMPLIANT.
THE DINING ROOM WAS CONVERTED INTO A BEDROOM. THIS ROOM ALSO DOES NOT MEET THE INTERNATIONAL RESIDENTIAL CODE REQUIREMENTS FOR A BEDROOM.
THE DINNING ROOM WHICH WAS CONVERTED INTO BEDROOM HAS THE WINDOW OBSTRUCTED BY STORAGE AND AN IRON GRATE BOLTED TO THE DWELLING, NO BREAK WAY HARDWARE.
ALL CEILING FANS WIRING METHODS IN THE BEDROOMS ARE NOT CODE COMPLIANT.
THE MASTER BATHROOM HAS A FALLEN LIGHT FIXTURE
THE MASTER BATHROOM WINDOW DOES NOT LOCK
THE HALLWAY HAS A MISSING COVER PLATE
THE KITCHEN FLOOR TILES ARE BROKEN
SINK IN THE MASTER BATHROOM WAS BACKED UP.
THE BATTERY POWERED SMOKE DETECTORS INSTALL ARE NOT CODE COMPLIANT AND MISSING IN REQUIRED AREAS
JACUZZI HOT TUB IN THE HALLWAY BATHROOM, NO PERMIT.
THE FRONT DOOR HAS A DOUBLE LOCKING KEY DEADBOLT
THERE IS A 20 X 20 WOOD FRAMED CARPORT LOCATED IN FRONT OF THE GARAGE, NO PERMIT OR ZONING APPROVALS.
THERE WAS A LIGHTING SYSTEM OVER THE POOL IN THE BACKYARD, THE TENANT WAS ASKED TO REMOVE THE SYSTEM. THE TENANT DID COMPLY.
THE MAIN DISCONNECT HAS MULTIPLE BREAKERS WITH NO LABELING
THE 60 AMP PANEL HAS A 20 AMP BREAKER WHICH WAS SHUT OFF DUE TO UNAPPROVED WIRING METHODS.
THE LAUNDRY ROOM HAS A RECEPTACLE TO THE DRYER WHICH IS NOT CODE COMPLIANT AND UNAPPROVED WIRING METHODS.
THE CONDITIONS INSIDE THE DWELLING ARE CLEAN AND OTHER THAN THE CODE VIOLATIONS LISTED ABOVE NO IMMEDIATE LIFE SAFETY CONCERNS. MANAGEMENT STATED THEY HAVE NO PROBLEM ALLOWING FIRST RESPONDERS ENTRY. DURING THIS INSPECTION THERE WERE NO MORE THAN 9 INDIVIDUALS PRESENT.