Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T21CM09962
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/07/2022 | ELECTRIC - SERVICE UPGRADE | Approved | Approved. The TEP clearance code is INCR. | |
| 02/03/2022 | ELECTRIC - SERVICE UPGRADE | Correction Required | CO Table 3603.4 requires a #4CU GEC for a 4/0AL ungrounded service conductor. Contractor has installed a #6CU. |