Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
02/07/2022 ELECTRIC - SERVICE UPGRADE Approved Approved. The TEP clearance code is INCR.
02/03/2022 ELECTRIC - SERVICE UPGRADE Correction Required CO
Table 3603.4 requires a #4CU GEC for a 4/0AL ungrounded service conductor. Contractor has installed a #6CU.