Permit: T21CM09946

Parcel: 136333830


Addresses:

9226 E 42ND ST

Inspection Status: Canceled

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
11/04/2022 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Canceled Inspection Canceled
03/11/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 2-5-25, provide a set of approved plans, firefoam all penetrations at top plate, missing"knockout" at subpanel, label all breakers, and install electrical covers for all receptacles. With regards to covered construction, provide a letter from a licensed contractor indicating that all covered construction was done per approved plans/ per the 2018 International Residential Code. If not possible, then covered construction would have to be uncovered to verify code compliance.

11 March 25
1. Same notes as above, no plans on site. Customer will submit for approval.