Inspection Status: Canceled
Inspection History: RSBU - Building Final
| Date |
Description |
Inspector |
Results |
Comments |
| 11/04/2022 |
RSBU - Building Final |
|
Canceled |
Inspection Canceled |
| 02/05/2025 |
RSBU - Building Final |
|
Re-inspection required |
2-5-25, provide a set of approved plans, firefoam all penetrations at top plate, missing"knockout" at subpanel, label all breakers, and install electrical covers for all receptacles. With regards to covered construction, provide a letter from a licensed contractor indicating that all covered construction was done per approved plans/ per the 2018 International Residential Code. If not possible, then covered construction would have to be uncovered to verify code compliance. |