Permit: T21CM09935

Parcel: 141410900

Inspection Status: Passed

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
03/31/2022 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing TLUNDBERG Approved Entered by NGARCIA3 - AP
03/30/2022 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing TLUNDBERG Cancelled Entered by VVERA1 - CA no plans on site
03/17/2022 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing TLUNDBERG Denied Entered by NGARCIA3 - DE The garage walk door trimmers have not been replaced and the blocking in the garage wall is not nailed off and flush with the framing. This is my 3rd inspection. PAY A REFEE BEFORE ANYMORE INSPECTIONS.
03/14/2022 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing TLUNDBERG Correction Required Entered by NGARCIA3 - CO Corrections incomplete 1. Missing 3 king studs next to 4x6 post at patio door. 2. Nail off blocking in garage wall 3. Trimmer studs are required to be continuous, without splices or blocks
03/10/2022 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing TLUNDBERG Correction Required Entered by VVERA1 - CO Missing king studs, garage blocking not nailed, missing HD anchors, incorrect header in garage walk door.