Inspection Status: Not Ready
Inspection History: COT - LCEL - Electrical Underground
Permit Number - T21CM09775
Inspection Description - COT - LCEL - Electrical Underground
Inspection Status - Not Ready
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/26/2022 | COT - LCEL - Electrical Underground | Not Ready | ||
| 03/11/2025 | COT - LCEL - Electrical Underground | Partial Pass | 3/11/25: (11) SCH 40 4" conduit stubbing out from MS1 10' running towards building 2 ok to backfill progress area. (4) SCH 40 4" from low voltage stubbing out | |
| 03/14/2025 | COT - LCEL - Electrical Underground | Partial Pass | 3-14-25, 5-SCH 40-1 1/2" conduits for fire pump room and panel verified per plans. Okay to backfill at progress areas. | |
| 03/18/2025 | COT - LCEL - Electrical Underground | Not Ready | 3-18-25, not ready | |
| 04/15/2025 | COT - LCEL - Electrical Underground | Partial Pass | 3/11/25: (11) SCH 40 4" conduit stubbing out from MS1 10' running towards building 2 ok to backfill progress area. (4) SCH 40 4" from low voltage stubbing out 10' 3-14-25, 5-SCH 40-1 1/2" conduits for fire pump room and panel verified per plans. Okay to backfill at progress areas. 3-18-25, not ready 4/15/25: electrical underground for 3 light pole bases on south east side of project approved to backfill. Ok to proceed |
|
| 11/06/2025 | COT - LCEL - Electrical Underground | Passed | 11-6-25: electrical underground approved. |