Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/24/2022 | EXT METAL CLIPS/EXT SHEATHING | Approved | AP | |
| 02/15/2022 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | NR | |
| 02/11/2022 | EXT METAL CLIPS/EXT SHEATHING | Correction Required | CO Follow detail 14/SD1.3 condition A for truss to shear wall connection |
|
| 02/10/2022 | EXT METAL CLIPS/EXT SHEATHING | Correction Required | CO 1. Opening at patio requires 3 king studs each end 2. Remove all nails between bottom cord of truss and shear wall top plate. |