Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T21CM09253
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/13/2022 | MECHANICAL - FINAL | Approved | Ap Called SWG Clear gas Close permit |
|
01/10/2022 | MECHANICAL - FINAL | Not ready for Inspection | nr Hvac and h2o heater ok with one exception. Tpr valve needs drain line down into pan. - land-locked unit. New gas lines run in house interior wall, to attic and roof, ok. However, the feed line from the meter to interior wall connection is under slab, which is not allowed. Line from meter to interior wall must go up the outside wall, into the attic, where it will connect to the verticle pipe dropping into the interior wall. Please take phone pictures of all piping and connections in the attic, as well as attic vent fixtures, for inspection, and redo pressure test. |