Permit: T21CM08578

Parcel: 10510059C

Inspection Status: Not Ready

Inspection History: COT - RSEL - Electrical Final 

Permit Number - T21CM08578

Inspection Description - COT - RSEL - Electrical Final 

Inspection Status - Not Ready

Date Description Inspector Results Comments
10/27/2022 COT - RSEL - Electrical Final  Not Ready
12/27/2023 COT - RSEL - Electrical Final  Re-inspection required 12/27/23: insulate main water line, vacuum breaker missing at main water line, water hammer arrester missing at dishwasher and refrigerator in all units, A/C on 2 end units being under amped requires 32.8amp min and 50 max, lock caps on refrigerant line on all units missing, properly secure bubble cover on unit 1 at outdoor receptacle, unit 204 missing bank plates at panel, ensure all refrigerant lines in attic are insulated, furnace in attics require disconnecting means within sight.
12/29/2023 COT - RSEL - Electrical Final  Passed