Inspection Status: Not Ready
Inspection History: COT - RSEL - Electrical Final
Permit Number - T21CM08578
Inspection Description - COT - RSEL - Electrical Final
Inspection Status - Not Ready
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/27/2022 | COT - RSEL - Electrical Final | Not Ready | ||
| 12/27/2023 | COT - RSEL - Electrical Final | Re-inspection required | 12/27/23: insulate main water line, vacuum breaker missing at main water line, water hammer arrester missing at dishwasher and refrigerator in all units, A/C on 2 end units being under amped requires 32.8amp min and 50 max, lock caps on refrigerant line on all units missing, properly secure bubble cover on unit 1 at outdoor receptacle, unit 204 missing bank plates at panel, ensure all refrigerant lines in attic are insulated, furnace in attics require disconnecting means within sight. | |
| 12/29/2023 | COT - RSEL - Electrical Final | Passed |