Inspection Status: Not Ready
Inspection History: COT - RSME - Mechanical Final
| Date |
Description |
Inspector |
Results |
Comments |
| 10/27/2022 |
COT - RSME - Mechanical Final |
|
Not Ready |
|
| 06/14/2022 |
COT - RSME - Mechanical Final |
DBENOIT |
Prior to Final Inspectn |
Entered by DBENOIT1 - AIR BALANCE REPORT REQUIRED TO FINAL INSPECTION |
| 12/27/2023 |
COT - RSME - Mechanical Final |
|
Re-inspection required |
12/27/23: insulate main water line, vacuum breaker missing at main water line, water hammer arrester missing at dishwasher and refrigerator in all units, A/C on 2 end units being under amped requires 32.8amp min and 50 max, lock caps on refrigerant line on all units missing, properly secure bubble cover on unit 1 at outdoor receptacle, unit 204 missing bank plates at panel, ensure all refrigerant lines in attic are insulated, furnace in attics require disconnecting means within sight. |
| 12/29/2023 |
COT - RSME - Mechanical Final |
|
Passed |
|