Inspection Status: Re-inspection required

Inspection History: COT - HCPL - Plumbing Intermediate 

Permit Number - T21CM08432

Inspection Description - COT - HCPL - Plumbing Intermediate 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
03/10/2023 COT - HCPL - Plumbing Intermediate  Re-inspection required Maintain 1" minimum clearance from B-vent to combustibles, Fill vent thru the roof, all electric to be #12 AWG per plan for bathroom and laundry room circuits, fire-block at soffit line, block 3 sides of register boxes
03/13/2023 COT - HCPL - Plumbing Intermediate  Re-inspection required Maintain 1" minimum clearance from B-vent to combustibles, Fill vent thru the roof, all electric to be #12 AWG per plan for bathroom and laundry room circuits, fire-block at soffit line, block 3 sides of register boxes

March 13th: remove all foam from B-vents and maintain min 1" clearance around vent to combustibles
Restroom switch & outlet require 12AWG.
NOTE: OK to one-side all interior walls and all ceilings
03/15/2023 COT - HCPL - Plumbing Intermediate  Partial Pass 3-15-23: All items from previous inspection cleared, except clearance from combustibles at water heater b vent. OK to proceed elsewhere. Reschedule when clearance is provided..
05/22/2023 COT - HCPL - Plumbing Intermediate  Passed