Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - HCPL - Plumbing Intermediate
Permit Number - T21CM08432
Inspection Description - COT - HCPL - Plumbing Intermediate
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/10/2023 | COT - HCPL - Plumbing Intermediate | Re-inspection required | Maintain 1" minimum clearance from B-vent to combustibles, Fill vent thru the roof, all electric to be #12 AWG per plan for bathroom and laundry room circuits, fire-block at soffit line, block 3 sides of register boxes | |
| 03/13/2023 | COT - HCPL - Plumbing Intermediate | Re-inspection required | Maintain 1" minimum clearance from B-vent to combustibles, Fill vent thru the roof, all electric to be #12 AWG per plan for bathroom and laundry room circuits, fire-block at soffit line, block 3 sides of register boxes March 13th: remove all foam from B-vents and maintain min 1" clearance around vent to combustibles Restroom switch & outlet require 12AWG. NOTE: OK to one-side all interior walls and all ceilings |
|
| 03/15/2023 | COT - HCPL - Plumbing Intermediate | Partial Pass | 3-15-23: All items from previous inspection cleared, except clearance from combustibles at water heater b vent. OK to proceed elsewhere. Reschedule when clearance is provided.. | |
| 05/22/2023 | COT - HCPL - Plumbing Intermediate | Passed |