Permit: T21CM08210

Parcel: 140380270


Addresses:

6817 S CRAYCROFT RD

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
05/06/2022 BUILDING - FINAL Approved AP
04/22/2022 BUILDING - FINAL Correction Required . CO
1. Install 4” house address numbers
2. Install a single outlet above microwave
3. Glazing at side walk door required to be tempered R308.4.2
4. Secure flex conduit at water heater
5. Install anti-thief device on AC Freon ports
6. All exterior outlets are required to be WR
7. Incorrect breaker size for AC
8. Paint all exterior pvc
9. Provide a tall ladder to access attic
10. Cut T&P line and 90 down toward grade. Install 90 on condensate line
11. Remove metal stake at water service, insulate all hose bibs and service