Inspection History Details
Inspection Status: Canceled
Inspection History: COT - RSEL - Outdoor Lighting
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/04/2022 | COT - RSEL - Outdoor Lighting | Canceled | Inspection Canceled | |
| 10/24/2025 | COT - RSEL - Outdoor Lighting | Re-inspection required | 10.24.25 Unit 1 Kitchen receptacles must be GFCI, minimum 2 separate circuits Water hammer arresters missing at dishwasher and washer box Bathroom GFCI non functional Mini split requires emission report to show that it is equal to or greater than US standard Outdoor receptacles must be WR Weather resistant and GFCI Labeling missing at panel schedule, open slots must be filled/covered (both panels) Unit 2 Mini split and ac unit require emissions test Water hammer arresters missing throughout Cover all receptacles GFCI required at kitchen, 2 circuits minimum |
|
| 12/01/2025 | COT - RSEL - Outdoor Lighting | Passed |