Permit: T21CM07854

Parcel: 106064110

Inspection Status: Not Ready

Inspection History: COT - LCME - Mechanical Final 

Permit Number - T21CM07854

Inspection Description - COT - LCME - Mechanical Final 

Inspection Status - Not Ready

Date Description Inspector Results Comments
10/26/2022 COT - LCME - Mechanical Final  Not Ready
08/31/2023 COT - LCME - Mechanical Final  Partial Pass 8/31/23: units 8132, 8131, 8129, and 8130 have AC units that are being over Amped by 30Amp fuses ( Max fuse is 25Amp), secure all electrical whips at rooftop AC units, AC units need condensate piping to be coated to prevent sun damage, All refrigerant lines on units 8129,8130,8131,8132 need to be coated to prevent sun damage on insulation. Receptacle on roof top needs to be WR and be provided with Weather cover, Junction box at roof top needs cover, Unit 3230 is missing cover at disconnect box, remove all excess conduit and wires on roof top.
10/10/2023 COT - LCME - Mechanical Final  Canceled Canceled per contractor. 10/10/2023
10/17/2023 COT - LCME - Mechanical Final  Passed