Permit: T21CM07444

Parcel: 140326310


Addresses:

5972 S ROWAN CT

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
09/23/2022 BUILDING - FINAL Approved Approved
09/21/2022 BUILDING - FINAL Denied Denied. Per previous notes
09/02/2022 BUILDING - FINAL Denied DE
1. Open slot in main panel
2. Label sub-panel breaker
3. Label all breakers in sub-panel
4. Exterior outlet required to be WR
5. Lights, outlets, and smoke detectors required to be arc-fault protected
6. Install a smoke detector outside of bedrooms
7. Cut clean-outs to grade and glue on threaded caps
8. Remove the flexible drain under vanity sink.
9. Hot/cold lines reversed at bathroom vanity
10. Provide the manufactures specs on insta-hot water heater
11. Wrap exterior water lines with min R-3 insulation