Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 01/24/2022 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
Approved, please send INCR Clearance to TEP for cutover |
| 01/11/2022 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
- Denied, Corrections required. Install continuous #4 bare CU & ground rods, remove Schedule 40 PVC raceway from location of new panel to existing location. (Not rated for direct sunlight, exceeds 360 degree bends.) provide permanent address label, install stand off supports for riser where exceeds 36” minimum above roof deck. |
| 11/02/2021 |
ELECTRIC - SERVICE UPGRADE |
|
Not ready for Inspection |
NR, no one home |
| 09/15/2021 |
ELECTRIC - SERVICE UPGRADE |
|
Not ready for Inspection |
NR, cancelled by Contractor |