Inspection History Details
Permit: T21CM06183
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/26/2022 | FIRE - FINAL | Approved | ||
| 05/19/2022 | FIRE - FINAL | Prior to Final Inspectn | 1. need knox sprinkler caps on all three buildings. 2. need FDC signs on all three buildings above the sprinkler connections. 3. walked 1145 venice and 4585 speedway placement ok. still need to walk one building that was not ready at this time. 1. Need knox boxes at the front entrances of all three buildings. 2. Need to remove keyed lock from gate in courtyard also need to either get a Knox pad lock to assure fire trucks can gain access to property from north west gate. |