Permit: T21CM05622

Parcel: 209170040


Addresses:

6505 S SANDARIO RD

Inspection Status: Passed

Inspection History: COT - LCEL - Electrical Underground 

Date Description Inspector Results Comments
02/10/2022 COT - LCEL - Electrical Underground  TGAUSP Approved Entered by NGARCIA3 - Approved and complete to panel rack, okay to backfill
01/19/2022 COT - LCEL - Electrical Underground  TLUNDBERG Partial Approval Entered by NGARCIA3 - PA 2 underground conduit @1” run from corner of storage building to future electric rack. Buried 24”
01/06/2022 COT - LCEL - Electrical Underground  TLUNDBERG Partial Approval Entered by NGARCIA3 - PA Approximately 160 l/f of 2 1/2”NM conduit and a 2”NM spare run from MCC2 to the north side of electrical control building.