Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/30/2021 | FIRE SPKLR - FINAL | Approved | ||
| 10/13/2021 | FIRE SPKLR - FINAL | Denied | -missing sprinkler coverage in closet in office area -Spray booth needs sprinkler coverage -Riser needs annual and 5 year internal inspections -Sprinkler flow bell is missing |