Inspection Status: Not Ready

Inspection History: COT - RSEL - Construction Power

Date Description Inspector Results Comments
10/26/2022 COT - RSEL - Construction Power Not Ready
09/14/2022 COT - RSEL - Construction Power SCARRAZCO Denied Entered by VVERA1 - denied. Panels have been contaminated and cannot be cleaned. Need to replace both main and sub panels.
07/21/2022 COT - RSEL - Construction Power SCARRAZCO Denied Entered by NGARCIA3 - DENIED. Panel needs to be 6’7" readily accessible. Remove paint from meter socket connections. No service entrance cables along with goose necks. No ufer/ ground rods.
10/21/2022 COT - RSEL - Construction Power Passed