Permit: T21CM04975

Parcel: 138020690


Addresses:

5736 S 12TH AV

Inspection Status: Canceled

Inspection History: COT - LCEL - Outdoor Lighting

Date Description Inspector Results Comments
11/04/2022 COT - LCEL - Outdoor Lighting Canceled Inspection Canceled
11/04/2022 COT - LCEL - Outdoor Lighting Canceled Inspection Canceled
01/16/2025 COT - LCEL - Outdoor Lighting Not Ready 1/17/24: permit extension
6/18/24: permit extension not ready
8/21/24: not ready
1/16/25: permit extension not ready
01/17/2024 COT - LCEL - Outdoor Lighting Not Ready 1/17/24: permit extension
03/27/2026 COT - LCEL - Outdoor Lighting Re-inspection required 3-27-26: adjust restroom door to 5pounds of pressure, secure mixing valve at restroom and insulate (ADA knee guards), secure emt cables/conduits above panel, remove tape from hood vent, add R3 insulation hot side of water heater, no power to receptacle adjacent to door by water heater, insulate backflow preventer, paint exterior plastic on rooftop, install permanent labeling at rooftop disconnect, Secure with electrical whip at A/C1's receptacle, rooftop receptacle must be weather resistant gfci, missing exhaust fan cap, seal around hood vent at rooftop.
04/01/2026 COT - LCEL - Outdoor Lighting Passed 4-1-26: outdoor lighting approved.
06/18/2024 COT - LCEL - Outdoor Lighting Not Ready 1/17/24: permit extension
6/18/24: permit extension not ready
08/21/2024 COT - LCEL - Outdoor Lighting Not Ready 1/17/24: permit extension
6/18/24: permit extension not ready
8/21/24: not ready