Inspection History Details
Inspection Status: Canceled
Inspection History: COT - LCBU - Building Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/04/2022 | COT - LCBU - Building Final | Canceled | Inspection Canceled | |
| 03/02/2026 | COT - LCBU - Building Final | Re-inspection required | 3-2-26: missing ADA restroom sign, grab bars must be installed 36" AFF-measured to the top of bars, mirror must be lowered to 40" to the reflective surface, adjust restroom door to 5 pounds of pressure, add R3 insulation to the hot leg of water heater, missing permanent panel label at sub panel, missing hammer arrestor at water closet, missing thermostatic valve at lavatory, missing studor vent-see details, provide ladder for roof access, remove several ceiling tiles so,that I may inspect above ceiling, provide manufactured specifications for Type B Hood, no power noted on receptacle located south of back door (by water heater), rubber couplings at water heater ABS not allowed, secure mc cabling behind water heater, schedule remaining inspections when ready. STOPPED INSPECTION-ADDITIONAL ITEMS MAY BE ADDED. | |
| 03/23/2026 | COT - LCBU - Building Final | Canceled | 3-23-26: canceled by contractor | |
| 03/27/2026 | COT - LCBU - Building Final | Re-inspection required | 3-27-26: adjust restroom door to 5pounds of pressure, secure mixing valve at restroom and insulate (ADA knee guards), secure emt cables/conduits above panel, remove tape from hood vent, add R3 insulation hot side of water heater, no power to receptacle adjacent to door by water heater, insulate backflow preventer, paint exterior plastic on rooftop, install permanent labeling at rooftop disconnect, Secure with electrical whip at A/C1's receptacle, rooftop receptacle must be weather resistant gfci, missing exhaust fan cap, seal around hood vent at rooftop. | |
| 04/01/2026 | COT - LCBU - Building Final | Partial Pass | 4-1-26: partial pass-pending condition and walk through of north side of building. | |
| 07/26/2024 | COT - LCBU - Building Final | Re-inspection required | Partial pending other inspections. 7/26/2024 ADA grab bars are too high along with the mirror. |