Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T21CM04892
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/19/2022 | MECHANICAL - FINAL | Approved | Ap Close permit Ok for C of O |
|
| 08/18/2022 | MECHANICAL - FINAL | Correction Required | 10 OF THE AC UNITS HAVE OSA FLOW RATES 52-97% BELOW REQUIRED FLOW RATE | |
| 08/12/2022 | MECHANICAL - FINAL | Partial Approval | Pa Pending air balance review. |
|
| 07/29/2022 | MECHANICAL - FINAL | Partial Approval | pa Units 205 - 212 all complete. |
|
| 06/30/2022 | MECHANICAL - FINAL | Partial Approval | -PA for Units 101, 102, 103, 104, 105, 201, 202, 203, and 204. | |
| 06/21/2022 | MECHANICAL - FINAL | Cancelled | Inspection canceled by contractor | |
| 06/21/2022 | MECHANICAL - FINAL | Cancelled | Inspection canceled by contractor |