Permit: T21CM04878

Parcel: 141153530


Addresses:

8080 S HOUGHTON RD

Inspection Status: Canceled

Inspection History: COT - LCEL - Electrical Final 

Date Description Inspector Results Comments
11/07/2022 COT - LCEL - Electrical Final  Canceled Inspection Canceled
01/04/2022 COT - LCEL - Electrical Final  TLUNDBERG Correction Required Entered by RSALDAT1 - CO 1. Support EMT within 36” of termination 2. Label all breakers in the panel in front of reach-in coolers 3. Replace the two 40A breakers with 30A breakers per manufactures specs