Permit: T21CM04720

Parcel: 12621002A

Inspection Status: Canceled

Inspection History: COT - RSME - Mechanical Final 

Permit Number - T21CM04720

Inspection Description - COT - RSME - Mechanical Final 

Inspection Status - Canceled

Date Description Inspector Results Comments
11/04/2022 COT - RSME - Mechanical Final  Canceled Inspection Canceled
11/01/2023 COT - RSME - Mechanical Final  Re-inspection required 11/1/23: GFCI receptacle missing at laundry room, all outdoor receptacles need to be WR, toilets need to be caulked, light fixture missing in bathrooms, receptacle under sink needs to be gfci and secured in box, range top missing, dishwasher receptacle has no power, properly secure water heater whip in storage room. insulate main water line, A/C unit condensate drain needs to be properly supported and connected to unit, A/C unit condensate drain needs to be coated for sun damage, pressure relief valve drainage at both water heaters need to fixed (The pipe should not be smaller than the outlet of the valve and must run full-size (no reductions) to the termination),exhaust duct for dryer requires backdraft damper. roof drain termination needs 90 degree to terminate to ground.
11/17/2023 COT - RSME - Mechanical Final  Passed