Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Canceled
Inspection History: COT - RSME - Mechanical Final
Permit Number - T21CM04720
Inspection Description - COT - RSME - Mechanical Final
Inspection Status - Canceled
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/04/2022 | COT - RSME - Mechanical Final | Canceled | Inspection Canceled | |
11/01/2023 | COT - RSME - Mechanical Final | Re-inspection required | 11/1/23: GFCI receptacle missing at laundry room, all outdoor receptacles need to be WR, toilets need to be caulked, light fixture missing in bathrooms, receptacle under sink needs to be gfci and secured in box, range top missing, dishwasher receptacle has no power, properly secure water heater whip in storage room. insulate main water line, A/C unit condensate drain needs to be properly supported and connected to unit, A/C unit condensate drain needs to be coated for sun damage, pressure relief valve drainage at both water heaters need to fixed (The pipe should not be smaller than the outlet of the valve and must run full-size (no reductions) to the termination),exhaust duct for dryer requires backdraft damper. roof drain termination needs 90 degree to terminate to ground. | |
11/17/2023 | COT - RSME - Mechanical Final | Passed |