Permit: T21CM04568

Parcel: 140420760

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
03/28/2022 ELECTRIC - INTERMEDIATE Approved AFTER HOURS INSPECTION FOR 400AMP MAIN BREAKER INSTALL @ EXISTING 2000AMP 277/480V SWITCHGEAR. THIRD PARTY ONSITE FOR HI POT TESTING. FIELD VERIFIED RESULTS AND OK TO RE ENERGIZE SES. VERBAL CLEARANCE SENT TO TEP INCR/RECN.
03/24/2022 ELECTRIC - INTERMEDIATE Partial Approval Partial, Construction meeting for after hours inspection, ok to schedule.
01/07/2022 ELECTRIC - INTERMEDIATE Partial Approval Partial, Electrical in walls complete ok to Sheetrock.
11/17/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial approval for Electrical in rooms 112, 113, and 109, okay to cover
11/10/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial. Electrical in walls ok for following rooms. (101,102,103,104,110)