Permit: T21CM04461

Parcel: 141210270


Addresses:

8800 E OLD VAIL RD

Inspection Status: Passed

Inspection History: COT - LCEL - Electrical Underground 

Date Description Inspector Results Comments
12/02/2021 COT - LCEL - Electrical Underground  TLUNDBERG Approved Entered by RSALDAT1 - AP Conduit and grounding to transformer pad approved as noted on page E4
11/24/2021 COT - LCEL - Electrical Underground  TLUNDBERG Not ready for Inspection Entered by NGARCIA3 - NR plans on site do not match completed work.
11/10/2021 COT - LCEL - Electrical Underground  DMUNIZ Partial Approval Entered by VVERA1 - Partial, west side 3 conduit runs N-S from pull box to pull box, to SES location. Ok to backfill progress areas.
11/03/2021 COT - LCEL - Electrical Underground  TLUNDBERG Partial Approval Entered by VVERA1 - PA Underground conduit and grounding approved as high lit Ed on page E-2.
10/21/2021 COT - LCEL - Electrical Underground  DMUNIZ Partial Approval Entered by NGARCIA3 - PARTIAL, CONDUITS FOR BRANCH CIRCUITS AND LIGHTING OK TO BACKFILL PROGRESS.