Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Passed
Inspection History: COT - LCEL - Electrical Underground
| Date |
Description |
Inspector |
Results |
Comments |
| 12/02/2021 |
COT - LCEL - Electrical Underground |
TLUNDBERG |
Approved |
Entered by RSALDAT1 - AP Conduit and grounding to transformer pad approved as noted on page E4
|
| 11/24/2021 |
COT - LCEL - Electrical Underground |
TLUNDBERG |
Not ready for Inspection |
Entered by NGARCIA3 - NR plans on site do not match completed work. |
| 11/10/2021 |
COT - LCEL - Electrical Underground |
DMUNIZ |
Partial Approval |
Entered by VVERA1 - Partial, west side 3 conduit runs N-S from pull box to pull box, to SES location. Ok to backfill progress areas.
|
| 11/03/2021 |
COT - LCEL - Electrical Underground |
TLUNDBERG |
Partial Approval |
Entered by VVERA1 - PA
Underground conduit and grounding approved as high lit Ed on page E-2.
|
| 10/21/2021 |
COT - LCEL - Electrical Underground |
DMUNIZ |
Partial Approval |
Entered by NGARCIA3 - PARTIAL, CONDUITS FOR BRANCH CIRCUITS AND LIGHTING OK TO BACKFILL PROGRESS.
|