Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/22/2022 |
ELECTRIC - FINAL |
|
Approved |
Approved. The TEP clearance code is DGC. |
| 04/12/2022 |
ELECTRIC - FINAL |
|
Denied |
DE. Approved plans show a 70 amp solar breaker for a 200 amp service. Actual buss rating is 200 amps per sticker. Additionally, Four Tesla power walls are installed, back-feeding through three separate panels, by a separate permit. Plans need review and revision by an EE to coordinate all of the above work. |