Inspection Status: Canceled
Inspection History: COT - FCON - Fire - Final
| Date |
Description |
Inspector |
Results |
Comments |
| 11/07/2022 |
COT - FCON - Fire - Final |
|
Canceled |
Inspection Canceled |
| 12/21/2021 |
COT - FCON - Fire - Final |
jfordney |
Denied |
Entered by JFORDNE1 - Verify ALL tampers
Waterflow switch on west riser (north) is stickinfg
Notification devices in vacant space not functioning |
| 12/10/2021 |
COT - FCON - Fire - Final |
jfordney |
Denied |
Entered by JFORDNE1 - Waterflow and tamper switches not connected to fire alarm. |
| 12/01/2021 |
COT - FCON - Fire - Final |
wmotto |
Cancelled |
Entered by WMOTTO1 - Inspection was cancled by the contractor. |
| 11/08/2021 |
COT - FCON - Fire - Final |
MRoss |
Partial Approval |
Entered by MROSS2 - Correct prinkler and fire alarm inspection defficiencies
Alarm T21FC00451 |