Permit: T21CM02823

Parcel: 134230710


Addresses:

6641 E COOPER ST

Inspection Status: Canceled

Inspection History: COT - RSME - Mechanical Final 

Date Description Inspector Results Comments
11/07/2022 COT - RSME - Mechanical Final  Canceled Inspection Canceled
04/21/2021 COT - RSME - Mechanical Final  RELEFANTE Denied Entered by VLEON1 - The fuses installed were a 50 amp, condenser calls for 40 amp. Breaker in main panel is 50 amp. Condenser calls for 40 amp main breaker